- 0086-(0)755-28125866 / 0086-13715349794
- 中文
Approvals
The B-Frame circuit breaker carries various approvals such as VDE, cURus, EAC, CCC and is CE certified. It is also recognised to UL 1077, UL 508 and listed to UL 489A.
Technical Data
Product Type |
B-Frame |
Ambient Operating Temperature |
-40°C to +85°C |
Endurance |
Minimum of 1000 operations with current (UL 489A Clause 12)* 6000 operations with current (UL 1077 Clause 22, UL 508 Clause 48)* |
Dielectric Strength |
1000 Vac plus twice the rated voltage for one minute (UL 489A Clause 8, UL 1077 Clause 23, UL 508 Clause 51)* |
Rated Impulse Withstand Voltage |
2.5 kV (IEC 60934 Clause 8.1.3.1.1)* |
Weight |
30 g single pole, 60 g double pole (unpacked) |
Altitude |
Certification tests done at altitude ≈ 2000 metres. Will operate at higher altitudes. |
Shock |
50 G to IEC 60068-2-27 |
Vibration |
10 G to MIL-STD-202F |
Flammability |
I3 - Ignition does not persist at 850°C after glow wire is withdrawn with an oxygen indexof ≥ 28 |
Toxicity |
F1 - Smoke indexof ≤ 20 which determines the fume class |
Pollution Degree |
PD2 - Normally only non-conductive pollution occurs. Temporary conductivity caused by condensation is to be expected. |
Accessories |
Mounting accessories, legend plate |
* Refer to the standard for details
Product Type |
Circuit Breaker |
Circuit Breaker |
Circuit Breaker |
Switch |
Approvals |
UL 1077, DIN / EN 60934, GB17701, CE, UKCA, EAC |
UL 489A, DIN / EN 60934, GB17701 |
GB14048.2 |
UL 508 |
Number of Poles |
1, 2 |
1 |
1, 2 |
2 (Series) |
Maximum Voltages |
240 Vac, 65 Vdc |
80 Vdc |
48 Vdc |
300 Vdc |
Current Ratings |
0.1 - 30 Aac, 0.1 - 25 Adc |
0.1 - 30 Adc |
0.5 - 15 Adc |
15 Adc |
Interrupting Capacity |
1 kA @ 240 Vac 0.5 kA @ 65 Vdc |
0.6 kA @ 80 Vdc 1.5 kA @ 65 Vdc (UL & GB only) |
1 kA |
- |
DC Polarity |
- |
Polarity sensitive |
|
|